| EPR
/ PVC
Three
Conductor Shielded
AEIC CS-6 MV-90 15kV
|
|
| A
P P L I C A T I O N S |
1.
2.
3.
4.
5. |
Raceways
Aerial (when properly supported)
Industrial plants
Primary power and distribution circuits
Utility substations
|
|
6.
7.
8.
9.
10.
|
Generating
plants
Wet or dry locations
Conduit, ducts, open tray or free air
Direct burial
Feeders, distribution, and branch circuits |
|
| S
P E C I F I C A T I O N S |
1.
2.
3.
4.
5.
6. |
Conductor:
Stranded soft-drawn bare copper
Conductor Shield: Semi-conducting compound or tape
Insulation: Ethylene propylene rubber (EPR)
Insulation Shield: Semi-conducting insulation screen
with a helically applied copper tape shield
Ground Wire: Stranded bare copper**
Cabling: suitable lay with fillers |
|
7.
8.
9.
10. |
Jacket:
Sunlight resistant polyvinyl
chloride (PVC)
Temperature: 90°C continuous,
130°C emergency, 250°C short circuit
Voltage: 15000 Volts 100% & 133% insulation
level
Industry Approvals:
UL 1072 listed type MV-90
ICEA S-68-516
NEMA WC8
AEIC CS-6 |
|
Part
Number |
Size
AWG/
MCM |
No.
of
Strands |
Ground
Size
AWG |
Insul.
Thick.
in |
Jacket
Thick.
in |
Approx.
O.D.
inches |
Amp.
*
Rating |
Approx.
Weight
lbs/Mft |
| 100%
Insulation Level |
| 04-FG-3807 |
2 |
7 |
6 |
.175 |
.110 |
1.90 |
165 |
1848 |
| 04-FG-3919 |
1 |
19 |
4 |
.175 |
.110 |
1.98 |
185 |
2088 |
| 04-FG-4019 |
1/0 |
19 |
4 |
.175 |
.110 |
2.07 |
215 |
2397 |
| 04-FG-4119 |
2/0 |
19 |
4 |
.175 |
.110 |
2.17 |
245 |
2787 |
| 04-FG-4219 |
3/0 |
19 |
3 |
.175 |
.110 |
2.28 |
285 |
3255 |
| 04-FG-4319 |
4/0 |
19 |
3 |
.175 |
.110 |
2.40 |
325 |
3817 |
| 04-FG-4437 |
250 |
37 |
3 |
.175 |
.110 |
2.50 |
360 |
4325 |
| 04-FG-4637 |
300 |
37 |
2 |
.175 |
.110 |
2.62 |
400 |
4675 |
| 04-FG-4837 |
350 |
37 |
2 |
.175 |
.110 |
2.73 |
435 |
5038 |
| 04-FG-5037 |
400 |
37 |
2 |
.175 |
.110 |
2.94 |
475 |
5757 |
| 04-FG-5337 |
500 |
37 |
1 |
.175 |
.110 |
3.08 |
535 |
7629 |
| 04-FG-5661 |
600 |
61 |
1 |
.175 |
.140 |
3.30 |
600 |
9350 |
| 04-FG-6061 |
750 |
61 |
1/0 |
.175 |
.140 |
3.53 |
670 |
11370 |
| 04-FG-6561 |
1000 |
61 |
1/0 |
.175 |
.140 |
3.77 |
770 |
13980 |
| 133%
Insulation Level |
| 04-FH-3807 |
2 |
7 |
6 |
.220 |
.110 |
2.10 |
165 |
2235 |
| 04-FH-3919 |
1 |
19 |
4 |
.220 |
.110 |
2.16 |
185 |
2371 |
| 04-FH-4019 |
1/0 |
19 |
4 |
.220 |
.110 |
2.25 |
215 |
2680 |
| 04-FH-4119 |
2/0 |
19 |
4 |
.220 |
.110 |
2.35 |
245 |
2982 |
| 04-FH-4219 |
3/0 |
19 |
3 |
.220 |
.110 |
2.46 |
285 |
3491 |
| 04-FH-4319 |
4/0 |
19 |
3 |
.220 |
.110 |
2.59 |
325 |
4153 |
| 04-FH-4437 |
250 |
37 |
3 |
.220 |
.110 |
2.69 |
360 |
4674 |
| 04-FH-4637 |
300 |
37 |
2 |
.220 |
.110 |
2.88 |
400 |
5387 |
| 04-FH-4837 |
350 |
37 |
2 |
.220 |
.140 |
2.97 |
435 |
6099 |
| 04-FH-5037 |
400 |
37 |
2 |
.220 |
.140 |
3.12 |
475 |
6970 |
| 04-FH-5337 |
500 |
37 |
1 |
.220 |
.140 |
3.26 |
535 |
8019 |
| 04-FH-5661 |
600 |
61 |
1 |
.220 |
.140 |
3.48 |
600 |
9780 |
| 04-FH-6061 |
750 |
61 |
1/0 |
.220 |
.140 |
3.71 |
670 |
11870 |
| 04-FH-6561 |
1000 |
61 |
1/0 |
.220 |
.140 |
3.95 |
770 |
14780 |
|
* Amps per conductor is in accordance
with NEC table 310-71, for three conductor copper cable isolated
in air, based on a conductor temperature of 90°C and ambient temperature
of 40°C. For other installation conditions, refer to the National
Electrical Code.
** Special ground wire configurations are available upon request
NOTE: May also be available with a Hypalon Jacket. |
|
|