| EPR
/ PVC
Single
Conductor
Shielded AEIC CS-6 MV-90 5/8 kV
|
|
| A
P P L I C A T I O N S |
1.
2.
3.
4.
5. |
Raceways
Aerial (when properly supported)
Industrial plants
Primary power and distribution circuits
Utility substations |
|
6.
7.
8.
9.
10. |
Generating
plants
Wet or dry locations
Conduit, ducts, open tray or free air
Direct burial
Feeders, distribution, and branch circuits |
|
| S
P E C I F I C A T I O N S |
1.
2.
3.
4. |
Conductor:
Stranded soft-drawn bare copper
Conductor Shield: Semi-conducting compound or tape
Insulation: Ethylene propylene rubber (EPR)
Insulation Shield: Semi-conducting insulation screen
with a helically applied copper tape shield
|
|
5.
6.
7.
8. |
Jacket:
Sunlight resistant polyvinyl
chloride (PVC)
Temperature: 90°C continuous,
130°C emergency, 250°C short circuit
Voltage: 5000 Volts
100% & 133% insulation level
8000 Volts, 100% insulation level
Industry Approvals:
UL 1072 listed type MV-90
ICEA S-68-516, NEMA WC8, AEIC CS-6 |
|
Part
Number |
Size
AWG/
MCM** |
No.
of
Strands |
Insul.
Thick.
in |
Jacket
Thick.
in |
Approx.
O.D.
inches |
Ampacity*
Rating |
Approx.
Weight
lbs/Mft |
| 04-AW-1334 |
6 |
7 |
.115 |
.060 |
0.66 |
75 |
300 |
| 04-AW-1336 |
4 |
7 |
.115 |
.060 |
0.71 |
97 |
370 |
| 04-AW-1338 |
2 |
7 |
.115 |
.060 |
0.77 |
130 |
475 |
| 04-AW-1339 |
1 |
19 |
.115 |
.060 |
0.81 |
155 |
545 |
| 04-AW-1340 |
1/0** |
19 |
.115 |
.060 |
0.85 |
180 |
635 |
| 04-AW-1341 |
2/0** |
19 |
.115 |
.080 |
0.93 |
205 |
780 |
| 04-AW-1342 |
3/0** |
19 |
.115 |
.080 |
0.98 |
240 |
910 |
| 04-AW-1343 |
4/0** |
19 |
.115 |
.080 |
1.04 |
280 |
1080 |
| 04-AW-1344 |
250** |
37 |
.115 |
.080 |
1.10 |
315 |
1230 |
| 04-AW-1348 |
350** |
37 |
.115 |
.080 |
1.20 |
385 |
1595 |
| 04-AW-1353 |
500** |
37 |
.115 |
.080 |
1.35 |
475 |
2155 |
| 04-AW-1360 |
750** |
61 |
.115 |
.080 |
1.54 |
600 |
3045 |
| 04-AW-1365 |
1000** |
61 |
.115 |
.080 |
1.69 |
690 |
3900 |
|
* Amps per conductor is in accordance
with NEC table 310-73, for three conductors in an isolated conduit
in air, based on a conductor temperature of 90°C and ambient temperature
of 40°C. For other installation conditions, refer to the National
Electrical Code.
** Sizes 1/0 and larger may be rated for CT use.
NOTE: May also be available with a Hypalon Jacket. |
|
|
JCH Wire & Cable... striving to exceed
customer expectations for quality, service, and value