| XLP/PVC
Single
Conductor
Shielded MV-90 5kV
|
|
| A
P P L I C A T I O N S |
1.
2.
3.
4.
|
Raceways
Aerial (when properly supported)
Industrial plants
Primary power & distribution circuits
|
|
5.
6.
7.
8.
9. |
Utility substations
Generating plants
Wet or dry locations
Conduit, ducts, open tray, or open air
Direct burial |
|
| S
P E C I F I C A T I O N S |
1.
2.
3.
4. |
Conductor:
Stranded soft-drawn bare copper
Conductor Shields: Semi-conducting compound or
tape
Insulation: Cross-linked polyethylene (XLP)
Insulation Shield: Semi-conducting compound or
tape with concentrically wrapped bare copper wires
|
|
5.
6
7.
8.
|
Jacket:
Polyvinyl chloride (PVC)
Temperature: 90°C continuous, 130°C emergency,
250°C short circuit
Voltage: 5000 Volts
100% + 133% insulation level
Industry Standards:
UL 1072 listed type MV-90 Wet or Dry,
ICEA S-66-524, NEMA WC 7, |
|
| Part
Number |
Size
AWG/
MCM |
No.
of
Strands |
Insul.
Thick.
in |
Jacket
Thick.
in |
Approx.
O.D.
inches |
Ampacity*
Rating |
Approx.
Weight
lbs/Mft |
| 100%
& 133% Insulation Level |
| 04-AF-1332 |
8 |
7 |
.090 |
.060 |
0.56 |
55 |
155 |
| 04-AF-1334 |
6 |
7 |
.090 |
.060 |
0.60 |
75 |
195 |
| 04-AF-1336 |
4 |
7 |
.090 |
.060 |
0.65 |
97 |
255 |
| 04-AF-1338 |
2 |
7 |
.090 |
.060 |
0.71 |
130 |
345 |
| 04-AF-1339 |
1 |
19 |
.090 |
.060 |
0.77 |
155 |
450 |
| 04-AF-1340 |
1/0 |
19 |
.090 |
.060 |
0.78 |
180 |
480 |
| 04-AF-1341 |
2/0 |
19 |
.090 |
.080 |
0.87 |
205 |
610 |
| 04-AF-1342 |
3/0 |
19 |
.090 |
.080 |
0.94 |
240 |
760 |
| 04-AF-1343 |
4/0 |
19 |
.090 |
.080 |
0.98 |
280 |
880 |
| 04-AF-1344 |
250 |
37 |
.090 |
.080 |
1.05 |
315 |
1045 |
| 04-AF-1348 |
350 |
37 |
.090 |
.080 |
1.12 |
385 |
1345 |
| 04-AF-1353 |
500 |
37 |
.090 |
.080 |
1.25 |
475 |
1840 |
| 04-AF-1360 |
750 |
61 |
.090 |
.080 |
1.45 |
600 |
2745 |
| 04-AF-1365 |
1000 |
61 |
.090 |
.080 |
1.63 |
690 |
3510 |
|
* Amps per conductor is in accordance
with NEC table 310-73, for three conductors in an isolated conduit
in air, based on a conductor temperature of 90°C and ambient temperature
of 40°C. For other installation conditions, refer to the National
Electrical Code.
NOTE: May also be available with a Hypalon Jacket. |
|
|
JCH Wire & Cable... striving to exceed
customer expectations for quality, service, and value